DuPont Nomex® 411 Paper Type Roll
MFR #:Nomex® 411-RL
EIS #:PH21-Nomex 411-RL
Series #:Nomex® 411-RL
MFR #:Nomex® 411-RL
EIS #:PH21-Nomex 411-RL
Series #:Nomex® 411-RL
Nomex® 411 is a lower-density version of Nomex® 410. It is used in applications such as motor phase insulation and transformer coil end filler, where high bulk and conformability are of prime importance. Visit our video channel to learn more about Paper Type Roll!
Nomex® 411 is a lower-density version of Nomex® 410. It is used in applications such as motor phase insulation and transformer coil end filler, where high bulk and conformability are of prime importance. Visit our video channel to learn more about Paper Type Roll!
Product Options
Length: 50 Yard | Thickness: 7 mil | Width: 38 Inch | EIS Part #: NMX4117N | $ / Square YD | ||
Length: 1520 Yard | Thickness: 7 mil | Width: 38 Inch | EIS Part #: NMX41175M | $ / Square YD |
- Attributes
- Features
- Applications
Attributes
General Information
Features
- Exceptional thermal stability - temperatures up to 200 °C have little or no effect on the electrical and mechanical properties of Nomex® and useful values are retained at considerably higher temperatures, What's more, these useful properties are maintained for at least 10 years of continuous exposure at 220 °C
- Outstanding mechanical toughness - densified Nomex® products are strong and resilient with good resistance to tearing and abrasion, thinner grades are also flexible
- Inherent dielectric strength in densified form, Nomex® withstands short-term electrical stresses of 18 kV/mm (457 mil) to 40 kV/mm (1015 mil), depending on product type and thickness, with no need for further treatment with varnishes or resins
- Broad chemical compatibility - Nomex® is essentially unaffected by most solvents and is unusually resistant to attacks by acids and alkalis. It is compatible with all classes of varnishes and adhesives, transformer fluids, lubricating oils and refrigerants
- Excellent flame resistance - Nomex® products do not melt and, with a limiting oxygen index (LOI) at 220 °C above 20.8 (the critical value for combustion in normal air), they do not support combustion
- 3 at 60 Hz (x 10^-3), 5 at 1 kHz (x 10^-3) dissipation factor
Applications
- Large Power, Medium Voltage and High Voltage (>1.2 kV), Medium Voltage, General Purpose (>1.2 kV), Medium Voltage, Substation (>1.2 kV), Low Voltage, General Purpose/Specialty (<1.2 kV), HVT/Microwave Power, UPS/Data Center/Converter, Lighting Ballast, Traction, Welding, Mining, Power Conversion